# Objective 1.4 — Reactive and Apparent Power

| LO# | Description |
|----------|----------|
| 1.4 | I can compute the reactive and apparent power values for an AC-powered circuit. |

By the end of this reading you should be able to:

1. Explain how **capacitors** and **inductors** shift the phase between voltage and current.
2. Distinguish **real power** $P$, **reactive power** $Q$, and **apparent power** $S$, and give the correct unit for each.
3. Use the **power triangle** to relate the three, and compute **power factor**.
4. Explain what a low power factor actually costs — the **current** it forces, not the VARs
   themselves — and how **power-factor correction** removes that cost.

## Beyond the Resistor

Objective 1.3 dealt only with resistors, where voltage and current stay in phase and
$P = V_\text{rms}I_\text{rms}$ tells the whole story. Real systems are not that tidy. Motors
have windings, cables have capacitance, and both introduce elements that store energy instead
of consuming it.

- A **capacitor** stores energy in an *electric* field. Current **leads** voltage by $90^\circ$.
- An **inductor** stores energy in a *magnetic* field. Current **lags** voltage by $90^\circ$.

Over a full cycle, each of these takes energy from the source and then gives all of it back.
Neither one consumes any net power.

:::{admonition} Key Concept
:class: key-concept

Reactive elements **borrow energy and return it**; resistors keep it. But a borrowed ampere is
still an ampere — it flows through the same generator, the same transformer, and the same
copper as a useful one, and it heats them just the same.
:::

## Where the Power Goes

When voltage and current are out of phase by an angle $\phi = \phi_V - \phi_I$, only the
component of current *in phase* with the voltage delivers energy. That fraction is $\cos\phi$:

$$
P = V_\text{rms}\,I_\text{rms}\cos\phi
$$

Check the two extremes:

- $\phi = 0^\circ$ (pure resistor) — $\cos\phi = 1$, so **all** of the product does work.
- $\phi = \pm 90^\circ$ (pure capacitor or inductor) — $\cos\phi = 0$, so **none** of it does.

Everything real falls between. The remainder is still flowing through the wires; it simply does
not accomplish anything.

## Three Kinds of Power

Because the product $V_\text{rms}I_\text{rms}$ splits into a useful part and a useless one, we
give each a name — and, importantly, **a different unit**, so that a glance at the units tells
you which quantity you are holding.

| Quantity | Symbol | Formula | Unit |
| --- | --- | --- | --- |
| Real power | $P$ | $V_\text{rms}I_\text{rms}\cos\phi$ | watts (W) |
| Reactive power | $Q$ | $V_\text{rms}I_\text{rms}\sin\phi$ | volt-amperes reactive (VAR) |
| Apparent power | $S$ | $V_\text{rms}I_\text{rms}$ | volt-amperes (VA) |

**Real power** is what does work and produces heat — the only one that shows up on an energy
bill. **Reactive power** is the energy sloshing in and out of the fields each cycle.
**Apparent power** is the total the source and the wiring must actually be built to carry.

## The Power Triangle

The three are not independent, and they do **not** add arithmetically. Because $P$ depends on
$\cos\phi$ and $Q$ on $\sin\phi$, they are perpendicular components of $S$:

$$
S^2 = P^2 + Q^2
$$

The angle between $S$ and $P$ is the same $\phi$ as between voltage and current, which gives
the **power factor**:

$$
\text{pf} = \cos\phi = \frac{P}{S}
$$

Power factor runs from 0 to 1. A power factor of 1 means every volt-ampere the source supplies
is doing useful work.

:::{admonition} Key Concept
:class: key-concept

$P$ and $Q$ are the legs of a right triangle and $S$ is the hypotenuse. A 3 kW load drawing
4 kVAR is **5 kVA**, not 7. Adding them arithmetically is the single most common error on this
objective.
:::

You will also hear power factor described as *lagging* or *leading*:

- **Lagging** — current lags voltage, so the load is **inductive**. Motors behave this way, and
  most industrial loads are lagging.
- **Leading** — current leads voltage, so the load is **capacitive**. Long cable runs and
  correction capacitors behave this way.

## Why Power Factor Costs Money

Reactive power does no work, so it is tempting to ignore it. The utility does not — but the
reason is more interesting than it first appears, and it is worth getting exactly right.

Here is the surprise: **reactive power itself consumes zero net energy.** Over each cycle, $Q$
is energy flowing into the load's magnetic or electric fields and then flowing straight back
out again. It averages to nothing. Your home electric meter reads kW·h, which is *real* energy,
so a homeowner running a badly reactive load pays **nothing extra** on that meter.

So if the VARs are free, what is the problem? **The problem is the current they require.** For
a fixed real power and voltage,

$$
I_\text{rms} = \frac{S}{V_\text{rms}} = \frac{P}{V_\text{rms}\,\text{pf}}
$$

Low power factor means more amperes for the same watts. And the amperes hurt, in three named
ways:

1. **$I^2R$ losses upstream.** Every extra ampere flows through the resistance of transmission
   lines, transformer windings, and building wiring, dissipating *real* power as heat along the
   way. That energy is genuinely consumed — just by the copper instead of by the load. Note the
   **square**: cutting the power factor in half doubles the current and **quadruples** the
   conduction loss.
2. **Equipment capacity.** Generators, transformers, cables, and switchgear are thermally
   limited by *current*, which is exactly **why they are rated in VA, not W**. A load at
   $\text{pf} = 0.5$ ties up **twice** the transformer capacity of a unity-power-factor load
   drawing the same real power. Someone has to build and maintain that capacity.
3. **Voltage regulation.** Reactive current flowing through the *reactance* of the lines drops
   the voltage. On transmission lines, where reactance dominates resistance, $Q$ is the main
   driver of voltage sag — and in the extreme, this mechanism is behind grid **voltage collapse**
   events.

Utilities know this well. Large **industrial and commercial** customers are billed with **kVA
demand charges** or **power-factor penalty clauses**, which commonly kick in once the power
factor drops below about **0.90 to 0.95**. **Residential** customers are not, and that is
exactly consistent with the physics: the meter on a house measures real energy only.

:::{admonition} Key Concept
:class: key-concept

**You pay for watts. You size the hardware for volt-amperes.** The gap between the two is what
power factor measures — and the payment shows up as copper losses, infrastructure capacity, and
(for large customers) explicit utility penalties, never as VARs on an energy meter.

**Nobody pays for the VARs. Everybody pays for the amperes the VARs require.**
:::

## Power-Factor Correction

Here is the satisfying payoff. The real villain is reactive current traveling *long distances*
through resistive wire — and since $Q$ can be generated anywhere, a lagging (inductive) load can
be fixed without touching the load at all.

Place a **capacitor bank right next to the inductive load**. The capacitor supplies leading VARs
that cancel the load's lagging VARs, so the reactive current now circulates in a **short local
loop** between the capacitor and the load instead of traversing the entire grid. From the
utility's point of view the combined load looks nearly resistive, $\text{pf} \approx 1$, and the
line current drops to nearly $I = P/V$. This is exactly what those big gray capacitor banks
bolted to poles and factory walls are doing.

![Circuit diagram: an AC grid source at the left feeds a long resistive line that carries only the real-power current I ≈ P/V, with the utility seeing a power factor of about 1. At the far end, a capacitor bank and an inductive load sit side by side on the same pair of nodes, and a highlighted loop with arrows shows the reactive current circulating locally between the capacitor and the load rather than returning down the long line.](./ECE215_Obj04_media/pf_correction.png)

Note what did *not* change: the load still draws exactly the same $Q$ it always did, and the
capacitor still stores and returns energy the way capacitors do. What changed is **where that
reactive current flows**. It no longer crosses the long, resistive line — so the $I^2R$ losses
fall, the line and transformer capacity is freed, and the voltage sag eases. All three harms are
attacked by moving the same current a shorter distance.

::::{admonition} Example Problem
:class: example-problem

A motor on a $240$ V RMS, 60 Hz line draws $15$ A RMS at a lagging power factor of **0.80**.
Find the apparent, real, and reactive power, and the phase angle.

**Understand:** The motor is an inductive load, so current lags voltage. We are given the two
RMS terminal quantities and the power factor, which is all three legs of the triangle in
disguise.

**Identify Key Information:**

- **Knowns:** $V_\text{rms} = 240$ V, $I_\text{rms} = 15$ A, $\text{pf} = 0.80$ lagging.
- **Unknowns:** $S$, $P$, $Q$, and $\phi$.
- **Assumptions:** Values given are RMS, as AC ratings always are unless stated otherwise.

**Plan:** Compute $S$ first — it needs no angle. Then use the power factor to get $P$, recover
$\phi$, and use it for $Q$. Finally check the triangle closes.

**Solve:**

$$
S = V_\text{rms}I_\text{rms} = (240)(15) = 3600\ \text{VA}
$$

$$
P = S\cos\phi = 3600(0.80) = 2880\ \text{W}
$$

$$
\phi = \cos^{-1}(0.80) = 36.9^\circ
$$

$$
Q = S\sin\phi = 3600\sin(36.9^\circ) = 2160\ \text{VAR}
$$

Check the triangle: $\sqrt{2880^2 + 2160^2} = 3600$ VA. ✓

**Answer:** $S = 3600$ VA, $P = 2880$ W, $Q = 2160$ VAR, $\phi = 36.9^\circ$. The line carries
3600 VA in order to deliver 2880 W of useful work.
::::

::::{admonition} Type-along
:class: type-along

An aircraft AC bus at $115$ V RMS, 400 Hz supplies a load drawing $20$ A RMS at a lagging power
factor of **0.90**.

1. Find $S$, $P$, $Q$, and $\phi$.
2. The generator is rated at $2.5$ kVA. Can it carry this load?
3. If the power factor were corrected to 1.0 while delivering the same real power, what current
   would the bus carry?

:::{admonition} Solution
:class: dropdown

**1.** $S = (115)(20) = 2300$ VA. $P = 2300(0.90) = 2070$ W.
$\phi = \cos^{-1}(0.90) = 25.8^\circ$, and taking the sine exactly rather than rounding through the
angle, $Q = 2300\sqrt{1 - 0.90^2} = 1002.55$, so $Q = 1003$ VAR.
Check: $\sqrt{2070^2 + 1002.55^2} = 2300$ VA. ✓

**2.** Yes — $2300$ VA is below the $2500$ VA rating, but only by about 8%. That is a thin
margin for a flight-critical bus.

**3.** At unity power factor, $S = P = 2070$ VA, so $I = 2070/115 = 18.0$ A, down from 20 A.

The same useful work is delivered with **10% less current**, which means less $I^2R$ loss in the
wiring, cooler conductors, and more headroom on the generator. That is exactly why power factor
correction exists.
:::

::::

## Method: Solving an AC Power Problem

1. Convert every given value to **RMS**.
2. Identify the **phase angle** $\phi$ — either directly, or from the power factor via
   $\phi = \cos^{-1}(\text{pf})$.
3. Compute $S = V_\text{rms}I_\text{rms}$. It requires no angle, so it is always the easiest.
4. Get $P = S\cos\phi$ and $Q = S\sin\phi$.
5. **Check** that $S^2 = P^2 + Q^2$.
6. Label every answer with its correct unit: W, VAR, or VA.

## Wrap-Up

Capacitors and inductors store and return energy rather than consuming it, so they draw current
without doing work. That splits the product $V_\text{rms}I_\text{rms}$ into **real power** $P$
(W), which does the work, and **reactive power** $Q$ (VAR), which does not — with **apparent
power** $S$ (VA) as the hypotenuse of the right triangle they form. The ratio $P/S$ is the
**power factor**, and the gap between what you use and what the hardware must carry is precisely
what it measures.

Objective 1.5 turns to a related question: once power reaches a device, how much of it comes out
the far side, and where does the rest go?