# Objective 1.6 — Transformers and Power Transmission

| LO# | Description |
|----------|----------|
| 1.6 | I can use a transformer's turns ratio, input voltages and currents, and output voltages and currents to calculate the efficiency, source voltage, and current of a power transmission system with one or more transformers.  |  

By the end of this reading you should be able to:

1. Explain why long-distance transmission must run at **high voltage**.
2. Relate primary and secondary voltage, current, and turns through the **turns ratio**.
3. Identify a transformer as **step-up** or **step-down** from $a$ alone.
4. Compute **line losses** and the overall **efficiency** of a transmission system.

## Power Transmission

Toward the end of the 19^th^ century, the first electric companies were
developing power transmission systems. At the heart of this difficult
engineering problem were losses due to line resistance over long
distances. For example, a typical power line has a loss of 250 mΩ/km.
When distances are small, we can ignore the relatively small resistance.
However, looking at the US national and regional power grid layout in
Figure 1, we see that power transmission distances are not usually
small.

![](./ECE215_Obj06_media/media/image1.png)

Figure 1: US national power grid

In most cases, the distance between substations and power generation
sites (dam, coal plant, nuclear plant, etc.) is over 20 km, resulting in
a line resistance of at least 5 Ω. Consider the efficiency of this
scenario, as in Figure 2, where we have a power plant producing DC power
then transmitting it across a large distance to a house, which consumes
12kW at 120V.

![](./ECE215_Obj06_media/media/image2.png)

Figure 2: Model of DC power transmission system

Since we already know how much power is consumed by the house (12 kW),
we need to figure out how much power is lost in the 5 Ω transmission
line. The best way to solve for this power is to determine the current.
Fortunately, the power plant, transmission line, and house are all in
series, which means they share the same current. All we need to do,
then, is determine the current of either the power plant or the house.
Since we are told nothing about the power plant, let's look at the
house. We know both the voltage drop across the house and the power
consumed by it. Solving the power equation for the current through the
house gives us

$$I = \ \frac{P_{House}}{V_{House}}\  = \ \ \frac{12\ kW}{120\ V}\  = \ \ 100\ A$$

Again, since this is a series circuit, the 100 A flows through each
device in the circuit. We can use this current to find the power lost in
the transmission line:

$$P_{Line} = IV_{Line} = I*IR_{Line} = \ I^{2}*R_{Line} = \ {(100\ A)}^{2}*5\ \mathrm{\Omega}\  = \ \ 50\ kW$$

Therefore, for every 12 kW of power that is used, 50 kW is wasted!

Hopefully, your intuition is already telling you this is not an
efficient way to deliver power. We can use the efficiency equation to
quantify how bad this option truly is. In order to provide 12kW to the
house and cover the loss in the transmission line, the power plant needs
to produce:

$$P_{PowerPlant} = P_{House} + P_{Line} = 12\ kW + 50\ kW = 62\ kW$$

Which allows us to calculate the efficiency as:

$$\eta = \ \frac{P_{USEFUL}}{P_{PRODUCED}} = \frac{P_{House}}{P_{PowerPlant}} = \ \frac{12\ kW}{62\ kW}\  = \ \ 19.35\%$$

Clearly, this is abysmal, and low efficiencies such as these would
increase electricity costs drastically. Fortunately, our power
transmission system uses AC power instead of DC power, which allows for
much higher efficiencies. The main benefit of AC power is that it allows
the use of transformers. Transformers allow the current to be reduced in
the transmission line. Reducing the current is a great strategy as the
current is typically the largest contributor to power losses.

:::{admonition} Key Concept
:class: key-concept

$a = N_1/N_2 = V_1/V_2 = I_2/I_1$. Note the **current term is inverted** — voltage and current move in opposite directions, because an ideal transformer conserves power.
:::

### Transformers

Ampere's Law states that an electric *current* running through a coil of
wire will induce a magnetic field. Similarly, Faraday's Law tells us
that a time-varying magnetic field induces a *voltage* in a wire. So,
even though a steady current induces a steady magnetic field, a steady
magnetic field does not induce any voltage. To take advantage of the
relationship between Ampere's law and Faraday's law, a time-varying
current can be used to induce a changing magnetic field that in-turn
induces a voltage. In fact, transformers rely on this so-called mutual
inductance. They are composed of two coils of wires (which are basically
inductors) wrapped around a common core, along with insulation to
isolate the two circuits.

The physical configuration of a transformer is shown on the left side of
Figure 3. The coil of wire on the left side is known as the *primary*
side, while the right side is known as the *secondary* side. The voltage
drop on the primary side is typically denoted by V<sub>p</sub> or V<sub>1</sub>, while the
secondary side's voltage drop is denoted by V<sub>s</sub> or V<sub>2</sub>. Finally, note
the ratio N<sub>1</sub>:N<sub>2</sub>, which is the *turns ratio* of the transformer. In
this case, N<sub>1</sub> is the number of turns in the primary, and N<sub>2</sub> the
number of turns in the secondary.

![](./ECE215_Obj06_media/media/image3.png)
![](./ECE215_Obj06_media/media/image4.png)

Figure 3: The physical configuration of a transformer and a transformer shown in a circuit
diagram.

In a transformer, the voltage per turn will be equal on both sides.
Since each winding is a series arrangement of turns, more turns on the
primary leads to a smaller voltage per turn. This happens because the
same voltage drop has to occur across more turns. On the secondary, each
turn increases the output voltage. This leads us to two interesting
points. First, more turns on the primary leads to a smaller voltage drop
on the secondary. Second, more turns on the secondary leads to a higher
voltage drop on the secondary. We can write this as the equation below.

$$V_{2} = V_{1}*\frac{N_{2}}{N_{1}}$$

Typically, this equation is rearranged to the form shown below.

---------------------------
**Key Concept**

$$a = \frac{N_{1}}{N_{2}} = \frac{V_{1}}{V_{2}}$$

If N<sub>2</sub> \< N<sub>1</sub>, then V<sub>2</sub> \< V<sub>1</sub>, and the transformer is called a
*step-down* transformer (a \> 1).

If N<sub>2</sub> \> N<sub>1</sub>, then V<sub>2</sub> \> V<sub>1</sub>, and the transformer is called a
*step-up* transformer (a \< 1).

---------------------------
The turns ratio is denoted by "a", and it is the number of turns in the
primary divided by the number of turns in the secondary (also the
voltage on the primary divided by the voltage on the secondary). The
efficiency of transformers is high by default, but advances in
technology over the last century allow us to make the assumption of zero
loss without sacrificing much rigor. Therefore, by assuming an ideal
transformer, power is conserved across the transformer's primary and
secondary sides, meaning input and output power are equivalent:

$$P_{1} = P_{2}$$

$${V_{1} \times I}_{1} = {V_{2} \times I}_{2}$$

$$\frac{V_{1}}{V_{2}} = \frac{I_{2}}{I_{1}}$$

Since the ratio of V<sub>1</sub> to V<sub>2</sub> is equal to the turns ratio, we can also
use the turns ratio to describe the relationship of the primary and
secondary currents:

$$a = \frac{N_{1}}{N_{2}} = \frac{V_{1}}{V_{2}} = \frac{I_{2}}{I_{1}}$$

Sometimes, when we draw transformers, it is more convenient to draw
block diagrams:

![](./ECE215_Obj06_media/media/image5.png)

Figure 4: Block diagram of a transformer with a voltage source and load

In block diagrams, everything is assumed to be in series, unless the
input or output of a device has multiple connections. In the example
above, the source is providing power through the line, which is then
connected to the transformer, with a turns ratio of a. The transformer
then transforms the voltage and current and provides power directly to
the load. This is a compact, concise way to draw electrical systems, and
we will use it frequently as we talk more about how systems behave,
rather than how individual circuits behave.

-----------------------
### Example Problem 1
A transformer with 100 turns on the primary and
50 turns on the secondary is used to deliver power from a 120-V<sub>rms</sub>
source to a 100-Ω load. How much power does the resistor consume? How
much power does the source provide?

![](./ECE215_Obj06_media/media/image6.png)

**Understand:** We have two circuits here that interact through a
transformer. On the left, the voltage source provides power to the
primary side of the transformer. At the right, the secondary side of the
transformer is effectively a new voltage source that drives the
resistor.

**Identify Key Information:**

-   **Knowns**: We know the source voltage, in V<sub>rms</sub>, the number of
    turns on both sides of the transformer, and the resistance of the
    load.

-   **Unknowns**: Power provided from the source, P<sub>Source</sub>, and power
    consumed at the resistor, P<sub>Resistor</sub>.

-   **Assumptions:** The transformer is an ideal transformer with no
    power loss.

**Plan:** Through KVL, we can find V<sub>1</sub> and then we can relate the two
circuits using the turns ratio information. Finally, we can use Ohm's
law and the power equation to find the power delivered to the load.

**Solve**: On the primary side of the transformer, applying KVL gives
V<sub>1</sub> = 120 V<sub>rms.</sub> Then, the turns ratio may be used to find V<sub>2</sub>.

$$a = \ \frac{N_{1}}{N_{2}}\  = \ \ \frac{100}{50}\  = \ \ 2$$

$$a = \frac{V_{1}}{V_{2}}$$

$$V_{2} = \frac{V_{1}}{a} = \frac{120\ V_{rms}}{2} = 60\ V_{rms}$$

This matches the expectation that for a \> 1, the transformer
*steps-down* the voltage when looking left to right.

On the secondary side of the transformer, applying KVL gives V<sub>R</sub> = 60
V<sub>rms</sub>. Using Ohm's Law:

$$I_{R} = \frac{V_{R}}{100\ \Omega} = \frac{60{\ V}_{rms}}{100\ \Omega} = 600\ {mA}_{rms}$$

Which is also I<sub>2</sub>, so we can now look back to finding I<sub>1</sub>, the primary
side current.

$$a = \frac{I_{2}}{I_{1}}$$

$$I_{1} = \frac{I_{2}}{2} = 300\ {mA}_{rms}$$

And then compute average power using RMS values:

$$P_{Source} = P_{PRIMARY} = I_{1}V_{1} = \left( 300\ mA_{rms} \right)\left( 120{\ V}_{rms} \right) = 36\ W$$

$$P_{Resistor} = P_{SECONDARY} = I_{2}V_{2} = \left( 600\ mA_{rms} \right)\left( 60{\ V}_{rms} \right) = 36\ W$$

This correlates with our intuition, as there is no modeled loss in the
circuit.

**Answer:** The source provides 36 W, and the resistor consumes 36 W of
average power.

-----------------

### Example Problem 2
An AC Power Plant is 10 km away from a
transformer with a turns ratio of 10 and a house that is using 12 kW of
power. The 20 km of electrical wire to and from the transformer has a
resistance of 5 Ω (roughly equivalent to a single 20 mm diameter
aluminum wire), and the home runs on 120 V<sub>rms</sub>. What is the efficiency
of the system?

![](./ECE215_Obj06_media/media/image7.png)

**Understand:** This system is very similar to the previous problem,
except the transmission line from the source to the primary side of the
transformer contains some loss (modeled as a 5Ω resistor).

**Identify Key Information:**

-   **Knowns:** Power consumed by the house, the voltage at the house,
    the turns ratio, and the line resistance

-   **Unknowns:** Power produced by the power plant the efficiency, η,
    of the system

-   **Assumptions:** The transformer is an ideal transformer with no
    power loss.

**Plan:** Our plan is to use P<sub>house</sub> and V<sub>house</sub> to find I<sub>2</sub>, then
use the turns ratio to find I<sub>1</sub>. At that point, we can find P<sub>Line</sub>.
Adding P<sub>Line</sub> to P<sub>House</sub> (which is the same as P<sub>2</sub>) will give the
total power the power plant must provide, P<sub>PowerPlant</sub>. Finally, we
will find η, which is:

$$\eta = \frac{P_{USEFUL}}{P_{USEFUL} + P_{LOSS}} = \ \frac{P_{USEFUL}}{P_{PRODUCED}}\  = \frac{P_{House}}{P_{PowerPlant}}$$

**Solve:** The power equation for the house, which is modeled as a
resistor, gives the current:

$$I_{house} = \frac{P_{house}}{V_{house}} = \frac{12\ kW}{120\ V_{rms}} = 100\ A_{rms}$$

Using KCL, we see I<sub>2</sub> is equal to I<sub>house</sub>. Using the turns ratio to
determine I<sub>1</sub>:

$$a = \frac{I_{2}}{I_{1}}$$

$$I_{1} = \frac{I_{2}}{10} = \frac{100{\ A}_{rms}}{10} = \ 10{\ A}_{rms}$$

The transmission line and the transformer's primary are in series, so
I<sub>Line</sub> = I<sub>1</sub>. Since we modeled the transmission line as a resistor,
we can use the power equation to solve for the power lost in the
transmission line.

$$P_{Line} = \ {I_{Line}}^{2}R_{Line} = \ \left( 10\ A_{rms} \right)^{2}*5\ \mathrm{\Omega}\  = \ 500W$$

The total power produced at the plant is the sum of all power consumed
in the system:

$$P_{PowerPlant} = P_{House} + P_{Line} = 12kW + 500W$$

Finally, we find the efficiency:

$$\eta = \ \frac{P_{USEFUL}}{P_{PRODUCED}}\  = \frac{P_{House}}{P_{PowerPlant}} = \ \ \frac{12kW}{12\ kW + 500W} = \frac{12kW}{12.5kW} = 96\%$$

**Answer:** The efficiency of this power transmission system is 96%.

Look back at the power transmission system in Figure 2. It is the same
as the one we just analyzed, with the exception of the transformer and
AC power source. By using AC power and a transformer, the efficiency of
a power transmission system can be increased from 19.35% to 96%!

----------------------
:::{admonition} Key Concept
:class: key-concept

Line loss is $I^2R_{line}$, computed with the current **in that segment** — not the load current. Using the wrong current here is the most common error on Quiz 3.
:::

### Block Diagrams

For the rest of this lesson, and much of the rest of the class, we will
represent circuits as block diagrams. The "XFMR" block will represent a
transformer. In later lessons, a block is labeled with the name of the
component it is representing.

----------------------
### Example Problem 3
You are managing a team tasked to create the
power supply system for a UAS controller station. The equipment consumes
640 W at a voltage of 25 V<sub>rms</sub>. The transmission line is modeled as a 5
Ω resistor. Contractors have submitted Options A and B. Option A uses a
transformer with a turns ratio of 10:1, while Option B uses a turns
ratio of 25:1. Calculate the efficiency and required generator voltage
for both options.

![](./ECE215_Obj06_media/media/image8.png)

**Understand:** Here we have a block diagram of a power transmission
system, which is nearly exactly the same as the previous problem. The
transmission line from the source to the transformer contains loss,
modeled as a 5Ω resistor.

**Identify Key Information:**

-   **Knowns:** We know the power consumed by the controller station,
    the voltage at which that power is provided, the

-   **Unknowns:** Efficiency (η) and the required source voltage (V<sub>S</sub>)
    for both options.

-   **Assumptions:** The transformer is an ideal transformer with no
    power loss.

**Plan:** Just as we did with the previous problem, we will find the
current to the controller station, then use the turns ratio to find V<sub>1</sub>
on the primary side of the transformer. Next, we will calculate the
power lost in the line and the voltage drop across the line. Finally, we
will find the voltage and power of the source, which will allow us to
calculate the efficiency of the system.

**Solve:** Notice first that this is a block diagram as opposed to a
circuit. The transformer is depicted as XFMR, which is a common
abbreviation. Notice there are only two currents in this system: I<sub>1</sub>,
which flows from the source through the transmission line to the primary
side of the transformer, and I<sub>2</sub>, which flows through the secondary
side of the transformer to the UAS controller.

We also know that V<sub>2</sub> = 25 V<sub>rms</sub> and that the average power consumed
by the UAS control station is 640 W.

Let's start by solving for both currents. Using the power equation:

$$P_{2} = I_{2}V_{2}$$

$$I_{2} = \ \frac{P_{2}}{V_{2}}\  = \ \ \frac{640\ W}{25\ V_{rms}}\  = \ \ 25.6\ A_{rms}.$$

We can now use the turns ratio to calculate I<sub>1</sub>:

$$a = \ \frac{N_{1}}{N_{2}} = \ \frac{I_{2}}{I_{1}}$$

$$I_{1} = \ \frac{I_{2}}{a}\  = \ \ \frac{25.6\ A_{rms}}{10}\  = \ 2.56\ A_{rms}$$

We can use this current to determine the power lost in the transmission
line and the efficiency of the system:

$$P_{Line}\  = \ \ {(I_{Line})}^{2}{*\ R}_{Line}$$

$$P_{Line}\ \  = \ \ \left( 2.56\ A_{rms} \right)^{2}*5\ \mathrm{\Omega} = 32.768\ W$$

$$\eta = \frac{P_{useful}}{P_{useful} + P_{loss}} = \ \ \frac{640\ W}{640\ W\  + 32.768\ W}\  = \ \ 95.13\%$$

At this point, we can solve for the voltages using the turns ratio:

$$a = \ \frac{N_{1}}{N_{2}} = \ \frac{V_{1}}{V_{2}}$$

$$V_{1} = \ a*\ V_{2}\  = \ \ 10*25\ V_{rms}\  = 250\ V_{rms}$$

It is important to realize V<sub>1</sub> is the voltage that drops across the
primary side of the transformer. It is not the same as the voltage that
drops across the power line, nor is it the same as the source voltage.
Both of these voltages can be calculated fairly easily, however, using
KVL and Ohm's Law:

$$V_{Line}\  = \ \ I_{Line}R_{Line} = \ \ 2.56\ A_{rms}*\ \ 5\ \mathrm{\Omega}\  = \ \ 12.8\ V_{rms}$$

$$V_{S} = \ V_{Line} + \ V_{1} = \ 12.8\ V_{rms} + \ 250\ V_{rms}\  = \ \ 262.8\ V_{rms}.$$

Therefore, Option A (with a 10:1 turns ratio) requires a 262.8 V<sub>rms</sub>
generator and has a 95.13 % efficiency.

![](./ECE215_Obj06_media/media/image9.png)

Now, let's do the same analysis for Option B.

![](./ECE215_Obj06_media/media/image10.png)

Since the power and voltage are the same as the previous option, we know
the current is also the same. Therefore,

$$I_{2}\  = \ \ 25.6\ A_{rms}.$$

Using the turns ratio equation,

$$I_{1} = \ \frac{I_{2}}{a}\  = \ \ \frac{25.6\ A_{rms}}{25}\  = \ \ 1.024\ A_{rms}$$

Solving for the power lost in the transmission line and the efficiency
of the system:

$$P_{Line}\  = \ \ {(I_{Line})}^{2}{*\ R}_{Line}$$

$$P_{Line} = {(1.024\ A_{rms})}^{2}*5\ \mathrm{\Omega} = 5.243\ W$$

$$\eta = \ \frac{P_{useful}}{P_{produced}}\  = \ \ \frac{640\ W}{640\ W\  + \ \ 5.243\ W}\  = \ \ 99.19\%$$

Finally, we can solve for V<sub>S</sub> with V<sub>Line</sub> and V<sub>1</sub>

$$V_{Line}\  = \ \ 1.024\ A_{rms}*\ \ 5\ \mathrm{\Omega}\  = \ \ 5.12\ V_{rms}$$

$$V_{1} = \ a*\ V_{2}\  = \ \ 25*25\ V_{rms}\  = 625\ V_{rms}$$

$$V_{S} = \ 5.12\ V_{rms} + \ 625\ V_{rms}\  = \ \ 630.1\ V_{rms}$$

With a turns ratio of 25:1, Option B requires a 630.1 V<sub>rms</sub> generator
and has a 99.19% efficiency.

**Answer:** Option A (with a turns ratio of 10:1) requires a 262.8
V<sub>rms</sub> generator and has a 95.13% efficiency while Option B (with a
turns ratio of 25:1) needs a 630.1 V<sub>rms</sub> generator and has a 99.19%
efficiency.

::::{admonition} Type-along
:class: type-along

A generator feeds a $1.5$ kW house load at $120$ V RMS, **unity power factor**, through a line with $R_{line} = 4\ \Omega$. A transformer with $a = 10$ steps down at the house end.

1. What current flows on the house side?
2. What are the transformer's *line-side* voltage $V_1$ and current $I_1$?
3. How much power is lost in the line, and what is the *drop* $V_{Line}$ across $R_{line}$?
4. Work back to the source: find $V_s$ and $I_s$.
5. What is the overall efficiency?

:::{admonition} Solution
:class: dropdown

**1.** $I_{house} = 1500/120 = 12.5$ A. (Unity power factor, so no pf divisor.)

**2.** The line side is the transformer's **primary**: $a = V_1/V_{house} = 10$, so $V_1 = 10(120) = 1200$ V. And $a = I_{house}/I_1$, so $I_1 = 12.5/10 = 1.25$ A — which is also the line current, because the line is in series with the primary.

**3.** $P_{line} = (1.25)^2(4) = 6.25$ W, and the drop across the line is $V_{Line} = I_1 R_{Line} = (1.25)(4) = 5$ V. $V_{Line}$ is that **drop**, not the 1200 V at the transformer — reading it as the line-side terminal voltage is what makes KVL fail to close.

**4.** KVL around the source loop: $V_s = V_1 + V_{Line} = 1200 + 5 = 1205$ V, and $I_s = I_1 = 1.25$ A (one series path from the source to the primary).

**5.** $\eta = 1500/(1500 + 6.25) = 99.59\%$. Without the transformer the same load would draw 12.5 A on the line, losing $(12.5)^2(4) = 625$ W — for 70.6% efficiency.
:::

::::

## Wrap-Up

Line loss goes as $I^2R_{line}$, so transmission runs at **high voltage and low current** — and since transformers need a *changing* flux, that is why the grid is AC. The turns ratio $a = N_1/N_2 = V_1/V_2 = I_2/I_1$ steps **up** when $a<1$ and **down** when $a>1$. Work backward from the load, and use the current that actually flows in each segment.

Objective 1.7 adds the other component that moves power between forms: the converter.