# Lesson 7 Flashcards — Reactive and Apparent Power

Click a question to reveal the answer.

<div data-flashcards data-deck="b1l7"></div>

<details>
<summary><strong>1. What do capacitors and inductors do to the phase between voltage and current?</strong></summary>
<div class="card-answer"><p>A capacitor makes current <em>lead</em> voltage by 90°; an inductor makes current <em>lag</em> by 90°. Both store and return energy each cycle rather than consuming it.</p></div>
</details>

<details>
<summary><strong>2. Do reactive elements consume real power?</strong></summary>
<div class="card-answer"><p><strong>No.</strong> They consume no real power — but they still draw current, and that current is real, as are the conductors that must carry it.</p></div>
</details>

<details>
<summary><strong>3. Define real, reactive, and apparent power with their units.</strong></summary>
<div class="card-answer"><p>All three use the same phase angle <span class="math notranslate nohighlight">\(\phi = \phi_V - \phi_I\)</span>. Real <span class="math notranslate nohighlight">\(P = V_\text{rms}I_\text{rms}\cos\phi\)</span> in watts (W). Reactive <span class="math notranslate nohighlight">\(Q = V_\text{rms}I_\text{rms}\sin\phi\)</span> in volt-amperes reactive (VAR) — and <span class="math notranslate nohighlight">\(Q\)</span> is <strong>signed</strong>: a lagging, inductive load has <span class="math notranslate nohighlight">\(\phi > 0\)</span> and <span class="math notranslate nohighlight">\(Q > 0\)</span>, a leading, capacitive load has <span class="math notranslate nohighlight">\(\phi < 0\)</span> and <span class="math notranslate nohighlight">\(Q < 0\)</span>. Apparent <span class="math notranslate nohighlight">\(S = V_\text{rms}I_\text{rms}\)</span> in volt-amperes (VA).</p></div>
</details>

<details>
<summary><strong>4. How do P, Q, and S combine?</strong></summary>
<div class="card-answer"><p>As a right triangle: <span class="math notranslate nohighlight">\(S^2 = P^2 + Q^2\)</span>. They are <strong>not</strong> added arithmetically — 3 kW with 4 kVAR is 5 kVA, not 7.</p></div>
</details>

<details>
<summary><strong>5. A load draws 2.3 kW at pf 0.92 lagging from a 115 V bus. Find the current and <span class="math notranslate nohighlight">\(Q\)</span>.</strong></summary>
<div class="card-answer"><p>Run the triangle backward. The power factor gives <span class="math notranslate nohighlight">\(S\)</span> from <span class="math notranslate nohighlight">\(P\)</span>: <span class="math notranslate nohighlight">\(S = P/\text{pf} = 2300/0.92 = 2500\ \text{VA}\)</span>. Then <span class="math notranslate nohighlight">\(S\)</span> gives the current: <span class="math notranslate nohighlight">\(I = S/V_\text{rms} = 2500/115 = 21.7\ \text{A}\)</span>. Then the triangle gives <span class="math notranslate nohighlight">\(Q\)</span> with its sign: <span class="math notranslate nohighlight">\(Q = +\sqrt{S^2 - P^2} = +\sqrt{2500^2 - 2300^2} = +\sqrt{960{,}000} = +980\ \text{VAR}\)</span> — <strong>positive</strong>, because the load is lagging.</p></div>
</details>

<details>
<summary><strong>6. Several loads share one bus. Which powers add?</strong></summary>
<div class="card-answer"><p><span class="math notranslate nohighlight">\(P\)</span> and <span class="math notranslate nohighlight">\(Q\)</span> add; <span class="math notranslate nohighlight">\(S\)</span> does <strong>not</strong>. Sum the real powers and the <em>signed</em> reactive powers — <span class="math notranslate nohighlight">\(P_\text{bus} = \sum P\)</span> and <span class="math notranslate nohighlight">\(Q_\text{bus} = \sum Q\)</span> — then rebuild the hypotenuse, <span class="math notranslate nohighlight">\(S_\text{bus} = \sqrt{P_\text{bus}^2 + Q_\text{bus}^2}\)</span>. Because the signs are kept, a leading load's <span class="math notranslate nohighlight">\(-Q\)</span> cancels a lagging load's <span class="math notranslate nohighlight">\(+Q\)</span>: two 4 kW loads at pf 0.80, one lagging and one leading, need 8 kVA of bus, not <span class="math notranslate nohighlight">\(5 + 5 = 10\)</span> kVA. That cancellation <em>is</em> power-factor correction.</p></div>
</details>

<details>
<summary><strong>7. Define power factor.</strong></summary>
<div class="card-answer"><p><span class="math notranslate nohighlight">\(\text{pf} = \cos\phi = P/S\)</span>, running from 0 to 1. A pf of 1 means every volt-ampere is doing useful work. Since <span class="math notranslate nohighlight">\(\cos\phi > 0\)</span> either way, always say <strong>leading</strong> or <strong>lagging</strong> alongside the number.</p></div>
</details>

<details>
<summary><strong>8. If reactive power does no work, why does a utility care about power factor?</strong></summary>
<div class="card-answer"><p>Because the current associated with <span class="math notranslate nohighlight">\(Q\)</span> still flows through generators, transformers, and wire, and that current hurts three ways. It causes <span class="math notranslate nohighlight">\(I^2R\)</span> <strong>losses</strong> in every conductor it crosses. It ties up <strong>capacity</strong> — the hardware is thermally limited by current, so it must be sized for <span class="math notranslate nohighlight">\(S\)</span> rather than <span class="math notranslate nohighlight">\(P\)</span>, which is why generators, transformers, and cables are rated in VA. And it degrades <strong>voltage regulation</strong>: reactive current through line reactance sags the voltage, the mechanism behind grid voltage collapse.</p></div>
</details>

<details>
<summary><strong>9. What does 'lagging' power factor tell you about the load?</strong></summary>
<div class="card-answer"><p>That current lags voltage, so the load is <strong>inductive</strong> — which is what a motor should be.</p></div>
</details>

<details>
<summary><strong>10. What are the two most common errors on this objective?</strong></summary>
<div class="card-answer"><p>Adding <span class="math notranslate nohighlight">\(P\)</span> and <span class="math notranslate nohighlight">\(Q\)</span> arithmetically instead of as a right triangle, and mixing peak with RMS values. Every equation here takes RMS.</p></div>
</details>

<details>
<summary><strong>11. A motor draws 15 A at 240 V with pf = 0.80 lagging. Find S, P, and Q.</strong></summary>
<div class="card-answer"><p><span class="math notranslate nohighlight">\(S = (240)(15) = 3600\ \text{VA}\)</span>; <span class="math notranslate nohighlight">\(P = S\cos\phi = 3600(0.80) = 2880\ \text{W}\)</span>; and <span class="math notranslate nohighlight">\(\phi = +\cos^{-1}(0.80) = +36.9^\circ\)</span> (lagging). Get the sine exactly rather than rounding through the angle: <span class="math notranslate nohighlight">\(\sin\phi = \sqrt{1 - 0.80^2} = 0.60\)</span>, so <span class="math notranslate nohighlight">\(Q = 3600(0.60) = +2160\ \text{VAR}\)</span> — positive, because the load is inductive. Check: <span class="math notranslate nohighlight">\(\sqrt{2880^2 + 2160^2} = 3600\)</span> ✓</p></div>
</details>

<details>
<summary><strong>12. What does correcting power factor to 1.0 achieve?</strong></summary>
<div class="card-answer"><p>The same real power is delivered with <em>less current</em>, so conductors run cooler, <span class="math notranslate nohighlight">\(I^2R\)</span> losses drop, and existing hardware can serve more load.</p></div>
</details>

<details>
<summary><strong>13. So what do customers actually pay for — the VARs themselves?</strong></summary>
<div class="card-answer"><p><strong>Nobody pays for the VARs.</strong> Reactive power consumes zero net energy: <span class="math notranslate nohighlight">\(Q\)</span> flows into the load's fields and straight back out each cycle, and a house meter reads kW&middot;h, which is <em>real</em> energy — so a homeowner pays nothing extra for a reactive load. What everybody pays for is the <strong>amperes the VARs require</strong>. At fixed <span class="math notranslate nohighlight">\(P\)</span> and <span class="math notranslate nohighlight">\(V\)</span>, <span class="math notranslate nohighlight">\(I = P/(V\,\text{pf})\)</span>, and those extra amperes cause <span class="math notranslate nohighlight">\(I^2R\)</span> losses upstream, tie up VA-rated equipment capacity, and sag the voltage. Large <strong>industrial and commercial</strong> customers see the bill directly, as <strong>kVA demand charges</strong> or <strong>power-factor penalty clauses</strong> that commonly kick in below a pf of about 0.90&ndash;0.95; residential customers do not.</p></div>
</details>